『Installation diagram of vortex flowmeter』Related information(clamp on meter|electromagnetic meter|venturi meterrotameter|orifice meter|ultrasonic flow meter|mass flow meter|coriolis mass flow meter|coriolis flow meter|magnetic flow meter|magmeter flow meter|magflow flow meter|mag meter flow meter|electromagnetic flow meter|vortex flow meter|turbine flow meter|thermal mass flow meter|thermal flow meter|rotameter flow meter)

1. Share the wiring method of the two-wire system for vortex flowmeter?
For the two-wire wiring method of the vortex flowmeter, please refer to the attached diagram. When you open the junction box, you can see a row of wiring terminals on the green circuit board. The first group is connected to the positive+24V power line, and the second group is connected to the current output signal accompanying wire. The two-wire wiring method here is 24V+and current I+. If this is a combination wiring, that is, the wiring method for the 4-20mA output of the two-wire system, be sure to pay special attention when wiring and do not connect it incorrectly.
2. Installation diagram of steam vortex flowmeter?
1. Vortex flowmeter has certain requirements for the upstream and downstream straight pipe sections of the installation point, otherwise it will affect the flow field of the medium in the pipeline and affect the measurement accuracy of the instrument. The length requirements for the upstream and downstream straight pipe sections of the instrument are shown in the figure. Note: The regulating valve should not be installed upstream of the vortex flowmeter as much as possible, but should be installed at 10D downstream of the vortex flowmeter. 2. The inner diameter of the upstream and downstream piping should be the same. If there is a difference, the inner diameter Dp of the piping and the inner diameter Db of the vortex flow meter body should meet the following relationship: 0.98Db ≤ Dp ≤ 1.05Db. The upstream and downstream piping should be concentric with the inner diameter of the flow meter body, and the different axial degrees between them should be less than 0.05Db. 3. The sealing gasket between the instru
_600x400.jpg)
3. Installation tips for vortex flowmeter, which company will install this?
1. Vortex buried street flowmeter can only measure unidirectionally. When installing, pay atte